Watlow Electric Gateway & DeviceNet Podręcznik Użytkownika Strona 191

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 232
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 190
Series D8 User’s Guide Chapter 7: Troubleshooting and Reconfiguring
Doc. 0600-3120-2000 Watlow Anafaze 173
Figure 7.4 Input Circuit
Current Inputs
For each current input, you must install a resistor. The value
of the resistor must be correct for the expected input range. In-
stall the resistor in the listed resistor pack (RP) location. Note
the resistor pack locations have three through-holes. Install
the resistor as shown in the illustration below.
Table 7.5 Resistor Values for Current Inputs
Resistor tolerance: ±0.1%
Table 7.6 Resistor Locations for Current In-
puts
Input Range Resistor Value RD
0 to 10 mA 6.0
0 to 20 mA 3.0
Loop
Resistor
Location RD
Loop
Resistor
Location RD
1 RP1 5 RP5
2 RP2 6 RP6
3 RP3 7 RP7
4 RP4 8 RP8
Com
IN-
RC (RTD)
IN+
RD
RP
Analog
Input
Terminal
Internal
RP
+5 Vdc
Reference
To D8
Circuitry
RC (Voltage)
+
-
RP#
RD
Przeglądanie stron 190
1 2 ... 186 187 188 189 190 191 192 193 194 195 196 ... 231 232

Komentarze do niniejszej Instrukcji

Brak uwag